Can You Answer Master & Journeyman Electrical Exam Calculation Questions With Ease?

Find the allowable ampacity for #10 gauge HSJO six conductor cord.

Solution:

Step #1

T.400-5(A)(1) provide ampacity values for HSJO cord: 35 amperes.

Step #2 

The ampacity that this table provides must be adjusted using T.400-5(A)(3) if the number of conductors that make up the cord exceeds three. Since in this case we have six conductor cord, a demand of 80% must be applied to the table’s ampacity value for this cord.

Step #3

Solve for allowable ampacity.

= Table ampacity  x  Table adjustment Factor

= 35 amps  x  80%

= 28 amps